FRP DUCTING DESIGN FEA SUMILATION
1.1 Introduction
This report aims to check the design adequacy of the modified rectangular header and branch duct branch.
This analysis is carried out with Finite Element analysis using Solidworks simulation static structure composite analysis.
The design of the ducts is based on the requirements of SMACNA.
Construction of the FRP ducts is by filament winding for the circular ducts and by hand lamination for the rectangular ducts. The material's properties have been taken from Win Fung Test figures for this construction.
For conservatism, a small reduction in properties have been assumed.
The corrosion barrier has been included in the structural calculations as per SMACNA as the environmental conditions are not severe. The corrosion barrier V,2M, is approx. 2.5mm thick.
1.2 Code & Reference Documents
a. Thermoset FRP Duct Construction Manual SMACNA
b. ASME RTP-1
c. PUB/WRP/CWRP-2/MXXX
d. P2E-CWRP-HSL-20-WF-D-001 $ 003
1.3 Design Parameters
Design Temperature Ambient
Design Pressure +/-7kPa & +/-9kPa As Required
Specific Gravity NA
Chemical Conditions Hydrogen Sulphide Gas
Resin System VE
Corrosion Barrier C Glass Veil + 900gsm CSM VE
Wind Loading Not Applicable
Location Singapore
1.5 Material Specification
As tested hand lamination figures for MWM construction
Tensile Strength 195MPa
Tensile Modulus 11.8GPa
Allowable laminate stress 19.5MPa
Figures For CSM
Tensile Strength 90MPa
Tensile Modulus 8 GPa
Allowable laminate stress 12Mpa